Voltage Relay with Timing and Counting Function AC380V
Applications Used in air conditioning units,elevator machine room,pumps,fans and other motor control applications,as pro
Description
Basic Info
| Model NO. | ZHRV2-45 |
| Action Principle | Electronic Type |
| Size | Miniature |
| Type | Voltage Relay |
| Rated Frequency | 50/60Hz |
| Rated Supply Voltage | AC220V~450V (3-Phase 3-Wire) |
| Phase Failure and Phase Sequence | <0.5s |
| Contact Configuration Capacity(a) | 10A |
| Short Circuit Protector Type | Nt00-6A |
| Output Type | 1c/O+1nc |
| Contact Capacity | Ue/Le:240V/1.5A,415V/0.95A |
| Net Weight | 200g |
| DIN Rail Standard | Width 35mm |
| Transport Package | Standard Packing |
| Specification | 80*44*65mm |
| Trademark | AKMAN |
| Origin | Zhejiang China |
| HS Code | 8536490000 |
| Production Capacity | 10000PCS/Week |
Product Description
ApplicationsUsed in air conditioning units,elevator machine room,pumps,fans and other motor control applications,as protection of over-volltage.under voltage,phase failure,phase sequence and phase unbalance. When the power supply is abnormal,turn off power supply to protect the equipment.
Features:
Built-in microprocessors,true RMS voltage measurement,voltage measurement acduracy ≤1%.Measuring frequency 45Hz~64Hz,button setting,LCD display voltage and fault information,protection can be rurned on or off.Check phase voltage balue by button,with N-phase phase failureprotection,DIN rail mounting.
Model Description
Function Setting Table
| Rated supply voltage | (3-phase 3-wire) 220V~450V AC |
| Rated supply frequency | 50Hz/60Hz |
| Phase failure and phase sequence | ≤0.5s |
| Delay error | ±10%+0.1s |
| Measurement accuracy | 1%, RMS |
| Data storage time | 10years |
| Maximum counting capacity | 999999 |
| Maximum timing capacity | 9999h59m |
| Maximum count frequency | 50Hz |
| Accumulated timing error | ≤1.001% |
| Count input signal | AC/DC 20V-450V |
| Contact configuration capacity(A) | 10A |
| IP Class | IP20 |
| Class of pollution | 3 |
| Electrical Life | 105 |
| Mechanical life | 106 |
| Altitude | ≤2000m |
| Allowable relative humidity | ≤50%(40ºC)(No condensation) |
| Use category | AC-15 |
| Short circuit protector type and maximum rating | NT00-6A |
| Contact capacity | Ue/le:240V/1.5A,415V/0.95A |
| Output type | 1C/O+1NC |
| DIN rail Standard | width 35mm(IEC/EN60715) |
Code Table
| Type | code | Technical parameter | Setting range | Factory setting | Step amount |
| Voltage setting | F11 | Over-voltage action value | OFF-381V~500V | 437V | 1V |
| F12 | Under-voltage action value | 260V~379V-OFF | 304V | 1V | |
| F13 | Over-voltage/Under-voltage hysteresis | 1~20V | 5V | 1V | |
| F14 | Unbalance action value | OFF-20V~80V | 32 | 1V | |
| Time setting | F15 | Unbalance hysteresis | 3V~15~ | 5V | 1V |
| FF21 | Over-voltage delay | 0.1~20S | 2s | 0.1S | |
| F22 | Under-voltage delay | 0.1~20S | 5s | 0.1S | |
| F23 | Unbalance delay | 0.1~20S | 2s | 0.1S | |
| F24 | delay | 0.3~30S | 2s | 0.1S | |
| F25 | Reset delay | 0.3~30S | 2s | 0.1S | |
| Protection Setting | F31 | Phase sequence protection | ON-OFF | ON | / |
| F32 | Self-reset function | ON | ON | / | |
| Function setting | F90 | Restore factory setting | ON | OFF | / |
| F91 | Timing & counting cleared | ON | OFF | / | |
| End | Exit setup |
Function diagram
Dimensions(mm)
Model significance:
ZHRV2-45 LCD display voltage relay, with timing and counting function, rated voltage range:3-phase 3-wire 220V~450V.
Prev: Naidian Jqx-38f-3z 40A/30A High Power Relay
Next: New Original Crouzet 88827103 Relay Time Delay Automatic Control Components Good Prices
Our Contact